electromagnetic suspension gas fire extinguishing
Product Description
The clean agent fire extinguishing system shall perform as outlined in the following sub-sections. Fm200 system; FM200 fire extinguisher The Technical Parameters Extinguishing Agent Extinguishing Agent Valve Drive Air Pressure System Power Supply System Working -10℃~55℃ System Protection Limits Area The largest single area 800m ²; System Start-up Mode Automatic system startup , Storage Bottle Volume
A. Achieve a 6.25% (v/v) extinguishing concentration for Class A (Surface Type Fires) hazards.
B. Achieve a 8.70% (v/v) or greater, as required, extinguishing concentration for Class B (Flammable Liquids) hazards.
C. Achieve a 7.00% (v/v) extinguishing concentration for Class C (Energized Electrical Equipment) hazards.
D. Within 10 seconds, the clean agent fire extinguishing system shall discharge 95% of the required suppression agent mass.
E. The clean agent HFC227 fire protection systems , FM200 gas fire extinguishing system shall consist of one or more Asenware Fire Systems agent cylinders and related equipment. The cylinders may be either connected to a discharge pipe arrangement separately or connected to a common manifold and discharge pipe arrangement. The agent cylinders shall be filled with FM-200, and super pressurized with dry nitrogen to a working pressure of 360 PSIG at 70°F (24.8 bar gauge at 21°C).
Product Name gas system Fire Extinguisher with free technical support Brand ASENWARE Model AW-FM200 Filling Pressure 4.2 Mpa
Release Time ≤10s
Filling Density ≤950kg/m3 6.0±1.0 Mpa(20℃) AC220V/DC24V/1A
Environment Temperature
Volume : the largest single area 3600m ³
electrical manual ,
mechanical emergency manual 40L, 70L, 100L, 120L, 150L
Product Categories : Fire Fighting Equipments > Gas Extinguishing Products